Notes for reuse of Lyboa pump of ZYD transformer oil filter

2019/8/1??????view:

  The pump must be stored in a dry place before it returns to the workplace again. Better at room temperature (200C). Before the pump is withdrawn from the workplace, it should be removed from the vacuum system, washed with dry nitrogen and replaced with oil. The inlet and outlet of the pump must be sealed with the shipping seals at the time of delivery. The gas town must be closed. If the pump is idle for a long time, it should be sealed with plastic bags and desiccant.

  If the pump has been idle for more than a year, it must be maintained in a standard way and oil must be changed before the pump is put into operation again. We recommend that you contact the LEYBOLD manufacturer for maintenance services.

  Standard pumps are not suitable for installation in explosive dangerous areas. Please contact us when you intend to apply this method. Before installing the pump, it must be reliably disconnected from the power supply in order to prevent accidental start-up of the pump. Pumps can only be installed by qualified and well trained personnel. All safety regulations should be observed.

  Installation of ZYD oil filter Lyboa pump for reuse:

  In order to ensure safe start-up, it is necessary to proceed step by step according to the following instructions.

  The start-up can only be carried out by trained full-time personnel.

  SOGEVAC can be installed on any flat, horizontal plane. Under the four legs, there are metric threaded holes for fixing pumps.

  If the pump is inclined, the oil level can not be correctly read out. The pump is in danger of running dry.

  According to the different use of oil, the ambient temperature of the pump should be between 12 (55) and 40 (104). By improving the pump or replacing different types of oil, the pump can operate at lower ambient temperature. Please consult us about these questions.

  In order to ensure a good cooling of the pump, there should be enough space in the intake and exhaust outlets for maintenance and repair. Make sure the motor air intake is clean and clean.

  1. Connect to the system

  Standard pumps are not suitable for installation in explosive dangerous areas. When you plan to do so, please consult us. Before installing the pump, it must be reliably cut off from the power supply to prevent unintentional starting of the pump. The pump can only be installed by qualified and trained professionals.

  Comply with all safety regulations.

  2. Inlet side

  The intake flange of the pump is connected by internal threads. The pump can be connected to the vacuum system with suitable connectors.

  The cross section of the intake pipe should be at least the same as that of the intake port. If the intake pipe diameter is too small, the pumping speed will be reduced.

  We recommend using LOCTITE or TEFLON tape for threaded joints to ensure vacuum sealing. (especially when dangerous gases)

  3. Installation Warning of ZYD Oil Filter Lyboa Pump

  The pump should be connected to the intake pipe without any stress. Hose or pipe fittings are used in intake and exhaust pipes for easy removal during pump maintenance.

  - The maximum import pressure shall not exceed atmospheric pressure (about 1013 mbar). When there is excessive pressure in the import, the pump shall not be started.

  - The type of material used in the installation of pipes should take into account the type of gas pumped. The same is true for seals.

  If the process gas contains dust, dust filters must be installed in addition to random dust filters. We recommend that dust filters be installed horizontally with tees (3/13) or elbows (3/14). This ensures that no dust particles fall into the intake when the filter is removed. Import filters with different filter elements. Metal filter can prevent solid particles such as paper and plastics from entering the pump; paper filter can remove small particles such as dust and powder less than 1 micron; activated carbon filter can absorb chemical vapor such as acid and solvent. If the activated carbon filter is stored in a humid place, it should be dried at 212 for 2 hours before use.

  When extracting steam, we recommend installing condensers at the inlet and outlet sides.

  When pumping dangerous gas, the intake pipe must be tight.

  Solid particles or liquids are never allowed to enter the pump.


主站蜘蛛池模板: 在线观看永久免费视频直播| 性色av一区二区三区| 久久久久成人精品无码| 最新97超级碰碰碰碰久久久久| 亚洲一级毛片免费看| 先锋夜色天堂码字幕区资源在线| 久久精品国产亚洲av无码娇色| 7777精品伊人久久久大香线蕉| 久久精品一区二区毛片| 亚洲性爱视频色站| 国产成人无码AV片在线观看| 真人黄网站亚洲欧美日韩| 亚洲色成人网站www观看入口| 精品人妻无码一区二区三区性| 欧美 卡通 色综合图区| www.AV啊啊啊| 三a级做爰片免费观看玉蒲团| 女优整片影音先锋| 亚洲激情图| 91人妻日韩人妻无码专区精品| 欧美女优在线天堂| 国产农村妇精品一二区| 精品国产高清自在线一区二区| 日产牛牛在线| 色色av网站| 国产欧美一区二区三区久久| 女人高潮抽搐喷液30分钟视频| 国产精品99久久久久久猫咪| 疯狂做受xxxx高潮欧美日本| 久久影院免费观看久久影院| 一级特黄性生活大片免费观看| 久久精品国产亚洲av高清热| 欧美一级欧美三级在线观看| 亚洲国产精品VA在线看黑人| 亚洲AV人人澡人人爽人人夜夜| 国产在线精品二区| 国产亚洲精品精品国产亚洲综合| 久久精品国产亚洲av忘忧草18| 521A∨在线播放| 女邻居掀开短裙让我挺进| 影音先锋色色色色色色色色色色色色色色|